4. Troubleshooting
WARNING!
Do not open or disassemble the S600 Inverter.
Attempting to service the unit yourself may cause an
electrical shock or fire.
Problems and Symptoms Possible Cause Solutions
Low output voltage Using average reading Use true RMS reading
meter and cable.
(110V195-105VAC,
Voltmeter.
(220V190-210VAC)
See page 11
3-4-7. of the manual
Load LED bar flash.
Overload Reduce load.
No output voltage Low input voltage. Recharge battery,
Voltage indicator check connections
In the lower red zone and cables.
No output voltage. Thermal shutdown Improve ventilation,
Over Temp indicator on make sure ventilation
shafts of the inverter
Load less than 600W are not obstructed.
Lower ambient
temperature.
No output voltage Short circuit or Wiring Check AC wiring
Overload indicator on error. for short circuit or
improper polarity (hot
and neutral reversed).
Very high power load Remove load.
16